| Mechanical | Size: 4-1/2" x 9" PC board |
| Mounting: Snap track |
| Environmental | Operating temperature: -40 to 158 deg. F (-40 to 70 deg. C) |
| Relative humidity: 5 to 90% non-condensing |
| Power requirements | Less than 70 mA minimum; 225 mA maximum @ 12 VDC |
| Input/Output | Digital inputs: Six optically isolated (12 VDC @ 10 mA). |
| All digital inputs can accumulate counts and time on in seconds (32-bit counters). |
| All digital inputs can be used as 30 Hz pulse accumulators (10 mS on/off to recognize state change). |
| Pulse inputs: Two pulse inputs (0 to 3 kHz), optically isolated. The high speed pulse inputs can also be used as status. |
| Digital outputs: Four optically isolated 100 mA driver outputs |
| Relay outputs: Two 12 A resistive @ 120 VAC form A |
| Analog inputs: Two 12-bit 4-20 mA |
| Communications | One RS-232/RS-485 port for communication |
| One RS-232 port for configuration |
| Protocols | MODBUS RTU protocol |
| Programming | Custom applications |